Features:
High-quality isolation transformer: H-class insulation material is used to ensure long-term stable operation.
The input switch comes from industry-leading brands such as Chint or optional Schneider to ensure high performance and reliability.
High efficiency: The maximum efficiency can reach 99%, which effectively saves energy.
Three-phase regulation: Provide independent or subordinate three-phase regulation to meet different load requirements.
Strong overload capacity: It can withstand 200% overload within 5 seconds and 150% overload within 1 minute to ensure safe and stable operation of the equipment.
Low energy loss: Reduce power waste and improve overall efficiency.
Comprehensive protection functions: Including overvoltage protection, overcurrent protection, phase loss/phase sequence error protection, delay protection and fault protection to ensure that the equipment is protected from power fluctuations and abnormal conditions.
Manual bypass: Red copper material is used to ensure higher durability and better electrical contact.
Remote control: Remote control is achieved through RS232 or RS485 interface (optional) for easy management and monitoring.
Protection level: IP23 (NEMA 2) for indoor use, IP54 (NEMA 3R) or IP65 for outdoor use, to meet the needs of various environments.
Highly customized design: According to customer needs, flexible customization options are provided to meet the specific requirements of different scenarios and equipment.
Voltage stabilizer block diagram
![]() |
![]() |
Specification
| Input Voltage range | Three phase 304V-456V , for wider range can be customized |
| Frequency | 50Hz/60Hz |
| Related voltage | Line voltage 380V |
| Voltage regulation accuracy | ±(1-7)% selectable (± 2.5% high precision) |
| Response time | <10ms |
| Stable schedule | ≤ 100ms |
| Waveform distortion | Not generate additional waveform distortion(static) |
| Effectiveness | 50KVA and below ≥97%, Above 50KVA ≥99% |
| Three-phase unbalance | Three-phase point voltage automatic balance |
| Delayed output | Regulate first, then output(protect the device from shock) |
| Overpressure | Output phase power is higher than 10%(245) |
| Under voltage | Output phase power is less than 10%(195) |
| Input | |
| Input voltage | 220V/380V,230V/400V,240V/415V etc or other voltage accepted |
| Phase | 3P+N+G or 3P+G option |
| Input range | ±20%(±15%~±60%) can be customized |
| Input frequency | 47Hz-63Hz |
| Input switch | Chint Brand switch(ABB,Schneider option) |
| Output | |
| Output voltage | 220V/380V,230V/400V,240V/415V etc or other voltage accepted |
| Phase | 3P+N+G or 3P+G option |
| Output accuracy | ±1%-±5%(factory setting 2%) |
| Output Frequency | 50Hz/60Hz (LCD display will be identify automatc 50 or 60Hz) |
| Power factor | 0.8 or 0.9,1 option( general AVR 0.8) |
| Waveform distortion | No distortion(same as input waveform) |
| Efficiency | ≥98%(on full load) |
| Overload capacity | 150% for 5 minutes,200% for 1 minute |
| Response time | <10ms |
| THD | <3%(linear load) |
| General | |
| Compensation transformer | Insulation H level,200 degree |
| Control method | Compensation regulation or Independent regulation for each phase (option) |
| Working principle | Full automatic ,servo motor/SCR/IGBT |
| IP level | IP21(indoor), IP54 or IP65(Outdoor) |
| Cooling | Air cooling/ Fan system |
| Environment | |
| Woking temperature | -20° to +50°(if high teperature in your city,please inform us) |
| Ralative humidity | <90% |
| Noise | 45db@70% load,55db@100%load (within one meter) |
| Altitude | <1500m |
| LCD display | |
| Display | 5.0 LCD digital dispaly |
| LCD display show | Input Phase to netural |
| Input phase to phase | |
| Output phase to neutral | |
| Output phase to phase | |
| Load Current in each phases(press button to switch ) | |
| Frequency (50 or 60hz autoamtic indentify show) | |
| Working temperature | |
| Function | |
| Normal functions | Malti-protect fuction,over voltage/under voltage protection,over current protection,over load protection,saty start protection,manual bypass protection,short circuit protection,lack of phase protection,wrong sequence protection,indicate alarm,over temperature protection. |
Application
CNC machine tools, laser cutting equipment
Medical equipment, electronic testing equipment
Industrial automation systems
Power and electrical equipment
Power transmission systems, metallurgical equipment, etc.