Main features:
Epoxy resin insulation:
The transformer adopts epoxy resin casting coil to achieve excellent electrical insulation performance and high reliability in adverse environments. EI type dry structure, no requirement for using lubricating oil, is environmentally friendly and safe, and can be used in sensitive environments.
High efficiency:
Efficiency >98%, extremely low energy loss during operation, economical and environmentally friendly.
Advanced cooling technology:
AN/AF cooling method ensures efficient heat dissipation, so that the transformer always operates at the optimum temperature.
Customized Output Voltage:
The output voltage can be tailored to suit your specific needs, including standard options such as 220V, 380V, 440V and 480V.
Good Short Circuit Withstanding:
Thanks to its high mechanical strength and solid construction, this transformer is able to withstand short circuit conditions, with enhanced durability and reliability.
Dry Design:
The dry design carries no risk of oil leakage, and the fire-resistant epoxy material makes it ideal for use in fire-prone areas.
Long Service Life:
The transformer is constructed to last long with minimal maintenance requirements and thus reduces operating costs.
Type designation
| Model: | S C (B) 13 – □ □ |
| S | Three phase |
| C | Solid molding(epoxy casting) |
| (B) | Low pressure foil coil |
| 11 | Performance level code |
| □ | Rated capacity (KVA) |
| □ | Rated voltage (high voltage KV) |
Main technical parameter
Technical parameters of SC(B)13 series 6kV, 10kV grade non-excitation voltage regulating distribution dry type transformer
| Rated capacity kVA | Voltage tap range | Connection symbol | No-load loss kW | Load loss kW | No-load current % | Short circuit impedance % | ||||
| HV kV | HV tap range % | LV kV | 130ºC(B)(100ºC) | 155ºC(F)(120ºC) | 180ºC(H)(145ºC) | |||||
| 30 | 6 6.3 6.6 10 10.5 11 |
±2.5 ±5 |
0.4 | Dyn11 Yyn0 |
0.135 | 0.605 | 0.64 | 0.685 | 1.42 | 4 |
| 50 | 0.195 | 0.845 | 0.9 | 0.965 | 1.44 | |||||
| 80 | 0.265 | 1.16 | 1.24 | 1.33 | 1.07 | |||||
| 100 | 0.29 | 1.33 | 1.41 | 1.52 | 1.09 | |||||
| 125 | 0.34 | 1.56 | 1.66 | 1.78 | 0.94 | |||||
| 160 | 0.385 | 1.8 | 1.91 | 2.05 | 0.93 | |||||
| 200 | 0.445 | 2.13 | 2.27 | 2.44 | 0.79 | |||||
| 250 | ±2×2.5 ±5 |
0.515 | 2.33 | 2.48 | 2.66 | 0.79 | ||||
| 315 | 0.635 | 2.94 | 3.12 | 3.35 | 0.72 | |||||
| 400 | 0.705 | 3.37 | 3.59 | 3.85 | 0.72 | |||||
| 500 | 0.835 | 4.13 | 4.39 | 4.7 | 0.72 | |||||
| 630 | 0.965 | 4.97 | 5.29 | 5.66 | 0.61 | |||||
| 630 | 0.935 | 5.05 | 5.36 | 5.76 | 0.61 | 6 | ||||
| 800 | 1.09 | 5.89 | 6.26 | 6.71 | 0.61 | |||||
| 1000 | 1.27 | 6.88 | 7.31 | 7.88 | 0.61 | |||||
| 1250 | 1.5 | 8.19 | 8.72 | 9.33 | 0.61 | |||||
| 1600 | 1.76 | 9.94 | 10.5 | 11.3 | 0.61 | |||||
| 2000 | 2.19 | 12.2 | 13 | 14 | 0.50 | |||||
| 2500 | 2.59 | 14.5 | 15.4 | 16.6 | 0.50 | |||||
| 1600 | 1.76 | 11 | 11.6 | 12.5 | 0.61 | 8 | ||||
| Rated Power | 1000 KVA |
| Input Voltage | 11kV, 12kV, 33kV (Customizable) |
| Output Voltage | 220V, 380V, 440V, 480V (Customizable) |
| Phase | 3 Phase |
| Frequency | 50/60Hz |
| Winding Material | Copper/Aluminum |
| Vector Group | Dyn11 |
| Efficiency | >98% |
| Cooling Method | AN/AF |
Applications:
Industrial Application:
Suitable for manufacturing factories, plants and warehouses with fixed power requirements and minimal downtime and maintenance needs.
Commercial Buildings:
Ideal for multi-storey office buildings, malls and centers which require stable power supply to meet the needs of equipment and systems.
Power Supply:
Suitable for transmission and distribution systems where high load requirement or strict demands on safety and fire performance characteristics are present.