Key Functions
- Motor control: V/F, vector and torque control with automatic load compensation.
- Speed and process control: Multi-step speed operation and built-in PID.
- Overload capacity: 150% rated current for 60 seconds; 200% for 1 second.
- Communication: Modbus RTU standard; optional PROFINET or PROFIBUS-DP.
- Protection: Overcurrent, overvoltage, overload, undervoltage and overtemperature protection, with fault records.

Typical Applications
| Application | Functions to consider |
|---|---|
| Production machinery and conveyors | Vector or torque control, multi-step speed operation |
| Water supply systems | PID control with a compatible feedback signal |
| Fans | Adjustable frequency and external speed references |
| Textile, rubber and plastics equipment | Torque compensation and multiple command sources |
The drive adjusts motor speed by changing output frequency and voltage. Set operating limits according to the motor and driven equipment; the VFD’s frequency range does not define the machine’s permissible speed range.
K950 Technical Specifications
| Parameter | Specification |
|---|---|
| Rated power range | 0.75–630 kW |
| Standard input | Three-phase 380V AC ±15% |
| Input frequency | 47–63 Hz |
| Output frequency | 0–500 Hz |
| Control modes | V/F, vector and torque control |
| Compatible motors | Asynchronous and synchronous motors; configuration must match the motor |
| Overload capacity | 150% rated current for 60 seconds; 200% for 1 second |
| Process functions | Multi-step speed control and PID |
| Braking | DC braking and dynamic braking; confirm required components |
| Communication | Modbus RTU standard; optional PROFINET / PROFIBUS-DP |
| Carrier frequency | 1–16 kHz, automatically adjustable |
| Analog input resolution | 12-bit |
| Ambient temperature | -10°C to +40°C; derating required at 40–50°C |
| Protection and cooling | IP20, forced-air cooling |
| Relative humidity | Up to 90%, non-condensing |
FAQ
Are the overload figures continuous ratings?
No. The specified overload capacity is 150% rated current for 60 seconds and 200% for 1 second. Confirm the drive’s suitability for the application’s normal current and repeated overload duty.
Does every K950 include PROFINET?
No. Modbus RTU is standard. PROFINET and PROFIBUS-DP require optional expansion modules.
Can I order a K950 with a different input voltage?
The standard supply is three-phase 380V AC ±15%. Confirm any alternative voltage and power-rating combination before ordering.
Request a K950 Configuration
Send your motor schedule, application details, control requirements, site conditions and quantity to request model selection, technical drawings and pricing.