Product Features:
- Reliable and Durable: Built to withstand tough conditions, providing stable performance with minimal maintenance.
- Efficient Power Distribution: Reduces the length of low-voltage lines, cutting power loss and improving supply quality.
- Energy-Saving Design: Uses a high-efficiency iron core to optimize energy use and lower operational costs.
- Space-Saving Installation: The pole-mounted design saves space and reduces infrastructure costs, ideal for areas with limited space.
- Reduced Power Losses: Low-voltage line losses are reduced by over 60%, making it highly efficient for power distribution.
Model meaning:
| Model: | D 11 – /□□□ | |||
| D | 11 | □ | □ | □ |
| Single -phase oil-immersed | Performance level code | The rated capacity(kVA) | Voltage level (kV) | Special used environment code |
Technical parameters
| Rated capacity(kVA) | Voltage Combinationand Tap range | Vector Group Symbol | No-load loss (W) | Load loss | No-load
current (%) |
Short circuit impedance (%)
4.0 |
||
| High pressure | High pressure tap range (%) | Low ressure (kV) | ||||||
| 5 | 6
6.3 10 10.5 11
|
±2×2.5
±5
|
0.22
0.23 0.24
|
iio
Ii6
|
40 | 215 | 3.2 | 3.5 |
| 10 | 45 | 235 | 2.8 | |||||
| 15 | 53 | 315 | 2.8 | |||||
| 20 | 62 | 405 | 2.8 | |||||
| 25 | 70 | 480 | 2.8 | |||||
| 30 | 80 | 560 | 2.8 | |||||
| 50 | 120 | 855 | 2.3 | |||||
| 63 | 135 | 1020 | 2.1 | |||||
| 80 | 160 | 1260 | 2.0 | |||||
| 100 | 190 | 1485 | 1.9 | |||||
| 125 | 220 | 1755 | 1.8 | |||||
| 160 | 260 | 2050 | 1.6 | |||||
Product Applications:
- Rural Power Grids: Ideal for providing reliable electricity to rural areas, enhancing both residential and agricultural power distribution.
- Energy-Saving Reconstruction: Can be used in energy-saving projects for urban power grids and railway networks.
- Remote and Scattered Villages: An efficient solution for areas with decentralized power supply needs.
- Industrial and Agricultural Use: Perfect for areas with high power consumption needs such as agricultural production and lighting.
Product Standards:
GB1094.1 ~ 2-2013
GB/T 6451-2015